Section 914.3.1.2 of the International Fire Code is hereby amended to read as follows:

914.3.1.2 Water supply to required fire pumps. In buildings that are more than 420 feet in building height, required fire pumps shall be supplied by connections to no fewer than two water mains located in different streets and shall not serve other buildings. Separate supply piping shall be provided between each connection to the water main and the pumps. Each connection and the supply piping between the connection and the pumps shall be sized to supply the flow and pressure required for the pumps to operate.

Exception: When approved by the Fire code official, two connections to the same main shall be permitted provided the main is valved such that an interruption can be isolated so that the water supply will continue without interruption through no fewer than one of the connections.

(Ord. 6532 § 2, 2020.)