Chapter 13.10
CONTROL OF BACKFLOW AND CROSS-CONNECTIONS

Sections:

13.10.010    Purpose.

13.10.020    Director of public works – Responsibility.

13.10.025    Building official – Responsibility.

13.10.030    Definitions generally.

13.10.040    Director of public works.

13.10.050    Approved defined.

13.10.060    Auxiliary water supply defined.

13.10.070    Backflow defined.

13.10.080    Back-siphonage defined.

13.10.090    Backflow preventer defined.

13.10.100    Contamination defined.

13.10.110    Cross-connection defined.

13.10.120    Cross-connection, controlled defined.

13.10.130    Cross-connection control by containment defined.

13.10.140    Hazard, degree of defined.

13.10.150    Industrial fluids system defined.

13.10.160    Pollution defined.

13.10.170    Water, potable defined.

13.10.180    Water, nonpotable defined.

13.10.190    Water service connection defined.

13.10.200    Water, used defined.

13.10.210    Water system defined.

13.10.220    Policies.

13.10.010 Purpose.

The purpose of this chapter is:

A. To protect the public potable water supply of the city from the possibility of contamination or pollution by isolating within its customers’ internal distribution system(s) or its customers’ private water system(s) such contaminants or pollutants which could backflow or back-siphon into the public water supply system;

B. To promote the elimination or control of existing cross-connections, actual or potential, between its customers’ in-plant potable water system(s) and nonpotable water systems, plumbing fixtures and industrial piping systems; and

C. To provide for the maintenance of a continuing program of cross-connection control which will systematically and effectively prevent the contamination or pollution of all potable water systems. (Ord. 1330 § 2, 1976.)

13.10.020 Director of public works – Responsibility.

The director of public works shall be responsible for the protection of the public potable water distribution system from contamination or pollution due to the backflow or back-siphonage of contaminants or pollutants through water service connections. If, in the judgment of the director of public works or designee thereof, an approved backflow prevention device is required at the city’s water service connection to any customer’s premises for the safety of the water system, the director of public works or designee thereof shall give notice in writing to the customer to install such an approved backflow prevention device at each service connection to his or her premises. The customer shall immediately install such approved device or devices at his own expense. Failure, refusal or inability on the part of the customer to install such device or devices immediately shall constitute grounds for discontinuing water service to the premises until such device or devices have been properly installed.

A. Backflow prevention devices should be tested immediately after installation, relocation or repair.

B. All persons testing backflow devices must be certified either by the American Water Works Association (California-Nevada section) or the Los Angeles County department of health services. (Ord. 07-1949 § 12, 2007; Ord. 1690 § 1, 1989; Ord. 1330 § 2, 1976.)

13.10.025 Building official – Responsibility.

The building official shall require all new construction regulated by the building code to comply with the requirements of this chapter and those provisions of the health code which affect new construction. (Ord. 1330 § 2, 1976.)

13.10.030 Definitions generally.

For the purpose of this title, the words and phrases set forth in CMC 13.10.050 through 13.10.210 shall have the meanings respectively ascribed to them in this chapter. (Ord. 1330 § 2, 1976.)

13.10.040 Director of public works.

The director of public works or designee thereof is vested with the authority and responsibility for the implementation of an effective cross-connection control program and for the enforcement of the provisions of this chapter. (Ord. 07-1949 § 13, 2007; Ord. 1330 § 2, 1976.)

13.10.050 Approved defined.

“Approved” means accepted by the water supervisor as meeting an applicable specification stated or cited in this chapter, or as suitable for the proposed use. (Ord. 1330 § 2, 1976.)

13.10.060 Auxiliary water supply defined.

“Auxiliary water supply” means any water supply on or available to the premises other than the purveyor’s approved public potable water supply. These auxiliary waters may include water from another purveyor’s public potable water supply or any natural source(s) such as a well, spring, river, stream, harbor, etc., or “used waters” or “industrial fluids.” These waters may be polluted or contaminated, or they may be objectionable and constitute an unacceptable water source over which the water purveyor does not have sanitary control. (Ord. 1330 § 2, 1976.)

13.10.070 Backflow defined.

“Backflow” means the flow of water or other liquids, mixtures or substances under pressure into the distributing pipes of a potable water supply system from any source or sources other than its intended source. (Ord. 1330 § 2, 1976.)

13.10.080 Back-siphonage defined.

“Back-siphonage” means the flow of water or other liquids, mixtures or substances into the distributing pipes of a potable water supply system from any source, other than its intended source, caused by the sudden reduction of pressure in the potable water supply system. (Ord. 1330 § 2, 1976.)

13.10.090 Backflow preventer defined.

A “backflow preventer” is one of the devices described below designed to prevent backflow or back-siphonage:

A. Airgap. “Airgap” is the unobstructed vertical distance through the free atmosphere between the lowest opening from any pipe or faucet supplying water to a tank, plumbing fixture, or other device and the flood level rim of said vessel. An approved airgap shall be at least double the diameter of the supply pipe, measured vertically, above the top of the rim of the vessel; and, in no case less than one inch. When an airgap is used at the service connection to prevent the contamination or pollution of the public potable water system, an emergency bypass shall be installed around the airgap system and an approved reduced pressure principal device shall be installed in the bypass system.

B. Reduced Pressure Principle Device. “Reduced pressure principle device” is an assembly of two independently operating approved check valves with an automatically operating differential relief valve between the two check valves, tightly closing shut-off valves on either side of the check valves, plus properly located test cocks for the testing of the check and relief valves. The entire assembly shall meet the design and performance specifications and approval of a recognized and city-approved testing agency for backflow prevention assemblies. The device shall operate to maintain the pressure in the zone between the two check valves at a level less than the pressure on the public water supply side of the device. At cessation of normal flow the pressure between the two check valves shall be less than the pressure on the public water supply side of the device. In case of leakage of either of the check valves the differential relief valve shall operate to maintain the reduced pressure in the zone between the check valves by discharging to the atmosphere. When the inlet pressure is two pounds per square inch or less, the relief valve shall open to the atmosphere. To be approved these devices must be readily accessible for in-line maintenance and testing and be installed in a location where no part of the device will be submerged.

C. Double Check Valve Assembly. “Double check valve assembly” is an assembly of two independently operating approved check valves with tightly closing shut-off valves on each side of the check valves, plus properly located test cocks for the testing of each check valve. The entire assembly shall meet the design and performance specifications and approval of a recognized and city-approved testing agency for backflow prevention devices. To be approved these devices must be readily accessible for in-line maintenance and testing. (Ord. 1330 § 2, 1976.)

13.10.100 Contamination defined.

“Contamination” means an impairment of the quality of the potable water by sewage, industrial fluids or waste liquids, compounds or other materials to a degree which creates an actual hazard to the public health through poisoning or through the spread of disease. (Ord. 1330 § 2, 1976.)

13.10.110 Cross-connection defined.

“Cross-connection” means any physical connection or arrangement of piping or fixtures between two otherwise separate piping systems one of which contains potable water and the other nonpotable water or industrial fluids of questionable safety, through which, or because of which, backflow or back-siphonage may occur into the potable water system. A water service connection between a public potable water distribution system and a customer’s water distribution system which is cross-connected to a contaminated fixture, industrial fluid system or with a potentially contaminated supply or auxiliary water system, constitutes one type of cross-connection. Other types of cross-connections include connectors such as swing connections, removable sections, four-way plug valves, spools, dummy sections of pipe, swivel or changeover devices, sliding multi-port tube, solid connections, etc. (Ord. 1330 § 2, 1976.)

13.10.120 Cross-connection, controlled defined.

“Controlled cross-connection” means a connection between a potable water system and a nonpotable water system with an approved backflow prevention device properly installed that will continuously afford the protection commensurate with the degree of hazard. (Ord. 1330 § 2, 1976.)

13.10.130 Cross-connection control by containment defined.

“Cross-connection control by containment” means the installation of an approved backflow prevention device at the water service connection to any customer’s premises where it is physically and economically infeasible to find and permanently eliminate or control all actual or potential cross-connections within the customer’s water system; or, it shall mean the installation of an approved backflow prevention device on the service line leading to and supplying a portion of a customer’s water system where there are actual or potential cross-connections which cannot be effectively eliminated or controlled at the point of cross-connections. (Ord. 1330 § 2, 1976.)

13.10.140 Hazard, degree of defined.

The “degree of hazard” is derived from an evaluation of the potential risk to public health and adverse effect of the hazard upon the potable water system.

A. Hazard – Health. Health hazard is any condition, device, or practice in the water supply system and its operation which could create, or in the judgment of the supervisor may create, a danger to the health and well-being of the water consumer. An example of a health hazard is a structural defect, including cross-connections, in a water supply system.

B. Hazard – Plumbing. Plumbing hazard is a plumbing-type cross-connection in a consumer’s potable water system that has not been properly protected by a vacuum breaker, air-gap separation or backflow prevention device. Unprotected plumbing-type cross-connections are considered to be a health hazard.

C. Hazard – Pollutional. Pollutional hazard is an actual or potential threat to the physical properties of the water system or to the potability of the public or the consumer’s potable water system or which would constitute a nuisance or be aesthetically objectionable or could cause damage to the system or its appurtenances, but would not be dangerous to health.

D. Hazard – System. System hazard is an actual or potential threat of severe damage to the physical properties of the public potable water system or the consumer’s potable water system or of a pollution or contamination which would have a protracted effect on the quality of the potable water in the system. (Ord. 1330 § 2, 1976.)

13.10.150 Industrial fluids system defined.

“Industrial fluids system” is any system containing a fluid or solution which may be chemically, biologically or otherwise contaminated or polluted in a form or concentration such as would constitute a health, system, pollutional or plumbing hazard if introduced into an approved water supply. This may include, but not be limited to: polluted or contaminated water; all types of process waters and “used waters” originating from the public potable water system which may have deteriorated in sanitary quality; chemicals in fluid form; plating acids and alkalies, circulated cooling waters connected to an open cooling tower and/or cooling towers that are chemically or biologically treated or stabilized with toxic substances; contaminated natural waters such as from wells, springs, streams, rivers, bays, harbors, seas, irrigation canals or systems, etc.; oils, gases, glycerine, paraffins, caustic and acid solutions and other liquid and gaseous fluids used in industrial or other purposes or for firefighting purposes. (Ord. 1330 § 2, 1976.)

13.10.160 Pollution defined.

“Pollution” means the presence of any foreign substance (organic, inorganic, or biological) in water which tends to degrade its quality so as to constitute a hazard or impair the usefulness or quality of the water to a degree which does not create an actual hazard to the public health but which does adversely and unreasonably affect such waters for domestic use. (Ord. 1330 § 2, 1976.)

13.10.170 Water, potable defined.

“Potable water” means any water which, according to recognized standards, is safe for human consumption. (Ord. 1330 § 2, 1976.)

13.10.180 Water, nonpotable defined.

“Nonpotable water” means water which is not safe for human consumption or which is of questionable potability. (Ord. 1330 § 2, 1976.)

13.10.190 Water service connection defined.

“Water service connection” is the terminal end of a service connection from the public potable water system; i.e., where the water purveyor loses jurisdiction and sanitary control over the water at its point of delivery to the customer’s water system. If a meter is installed at the end of the service connection, then the service connection shall mean the downstream end of the meter. There should be no unprotected takeoffs from the service line ahead of any meter or backflow prevention device located at the point of delivery to the customer’s water system. Service connection shall also include water service connection from a fire hydrant and all other temporary or emergency water service connections from the public potable water system. (Ord. 1330 § 2, 1976.)

13.10.200 Water, used defined.

“Used water” means any water supplied by a water purveyor from a public potable water system to a consumer’s water system after it has passed through the point of delivery and is no longer under the sanitary control of the water purveyor. (Ord. 1330 § 2, 1976.)

13.10.210 Water system defined.

The water system is made up of two parts: the utility system and customer’s system.

A. The utility system consists of the source facilities and the distribution system and includes all those facilities of the water system under the complete control of the utility, up to the point where the customer’s system begins.

1. The source includes all components of the facilities utilized in the production, treatment, storage, and delivery of water to the distribution system.

2. The distribution system includes the network of conduits used for the delivery of water from the source to the customer’s system.

B. The customer’s system shall include those parts of the facilities beyond the termination of the utility distribution system which are utilized in conveying utility-delivered domestic water to points of use. (Ord. 1330 § 2, 1976.)

13.10.220 Policies.

The following policies shall apply to all water service connections in the city:

A. No water service connection to any premises shall be installed or maintained by the water purveyor unless the water supply is protected as required by state laws and regulations and this chapter. Service of water to any premises shall be discontinued by the water purveyor if a backflow prevention device required by this chapter is not installed, tested and maintained, or if it is found that a backflow prevention device has been removed, bypassed, or if an unprotected cross-connection exists on the premises. Service will not be restored until such conditions or defects are corrected.

B. The customer’s system should be open for inspection at all reasonable times to authorized representatives of the division to determine whether cross-connections or other structural or sanitary hazards, including violations of these regulations, exist. When such a condition becomes known, the supervisor shall deny or immediately discontinue service to the premises by providing for a physical break in the service line until the customer has corrected the condition(s) in conformance with state and city statutes relating to plumbing and water supplies and the regulations adopted pursuant thereto.

C. An approved backflow prevention device shall also be installed on each service line to a customer’s water system at or near the property line or immediately inside the building being served; but, in all cases, before the first branch line leading off the service line wherever the following conditions exist:

1. In the case of premises having an auxiliary water supply which is not or may not be of safe bacteriological or chemical quality and which is not acceptable as an additional source by the supervisor, the public water system shall be protected against backflow from the premises by installing a backflow prevention device in the service line appropriate to the degree of hazard.

2. In the case of premises on which any industrial fluids or any other objectionable substance is handled in such a fashion as to create an actual or potential hazard to the public water system, the public system shall be protected against backflow from the premises by installing a backflow prevention device in the service line appropriate to the degree of hazard. This shall include the handling of process waters and waters originating from the utility system which have been subject to deterioration in quality.

3. In the case of premises having (a) internal cross-connections that cannot be permanently corrected and controlled, or (b) intricate plumbing and piping arrangements or where entry to all portions of the premises is not readily accessible for inspection purposes, making it impracticable or impossible to ascertain whether or not dangerous cross-connections exist, the public water system shall be protected against backflow from the premises by installing a backflow prevention device in the service line.

D. The type of protective device required under subsections (C)(1), (2), and (3) of this section shall depend upon the degree of hazard which exists as follows:

1. In the case of any premises where there is an auxiliary water supply as stated in subsection (C)(1) of this section and it is not subject to any of the following rules, the public water system shall be protected by an approved airgap separation. A reduced pressure principle backflow prevention device may be used if the device is approved by the State Department of Health Services and the city water division.

2. In the case of any premises where there is water or substance that would be objectionable but not hazardous to health if introduced into the public water system, the public water system shall be protected by an approved double check valve assembly.

3. In the case of any premises where there is any material danger to health which is handled in such a fashion as to create an actual or potential hazard to the public water system, the public water system shall be protected by an approved airgap separation or an approved reduced pressure principle backflow prevention device. Examples of premises where these conditions will exist include sewage treatment plants, sewage pumping stations, chemical manufacturing plants, hospitals, mortuaries and plating plants.

4. In the case of any premises where there are “uncontrolled” cross-connections, either actual or potential, the public water system shall be protected by an approved airgap separation or an approved reduced pressure principle backflow prevention device at the service connection.

5. In the case of any premises where, because of security requirements or other prohibitions or restrictions it is impossible or impractical to make a complete in-plant cross-connection survey, the public water system shall be protected against backflow or back-siphonage from the premises by the installation of a backflow prevention device in the service line. In this case, maximum protection will be required; that is, an approved airgap separation or an approved reduced pressure principle backflow prevention device shall be installed in each service to the premises.

E. Any backflow prevention device required herein shall be of a model and size approved by the supervisor. The term “approved backflow prevention device” means a device that has been manufactured in full conformance with the standards established by the American Water Works Association entitled:

AWWA C506-69, Standards for Reduced Pressure Principle and Double Check Valve Backflow Prevention Devices:

and, have met completely the laboratory and field performance specifications of the Foundation for Cross-Connection Control and Hydraulic Research (FCCC&HR) of the University of Southern California established by:

Specifications of Backflow Prevention Devices – #69-2 dated March 1969 or the most current issue.

Said AWWA and FCCC&HR standards and specifications have been adopted by the supervisor. Final approval shall be evidenced by a certificate of approval issued by an approved testing laboratory certifying full compliance with said AWWA standards and FCCC&HR specifications.

The following testing laboratory has been qualified by the supervisors to test and certify backflow preventers:

Foundation for Cross-Connection Control and Hydraulic Research

University of Southern California

University Park

Los Angeles, California 98007

Testing laboratories other than the laboratory above will be added to an approved list as they are qualified by the supervisors. Backflow preventers which may be subjected to back pressure or back-siphonage that have been fully tested and have been granted a certificate of approval by said qualified laboratory and are listed on the laboratory’s current list of approved devices may be used without further test or qualification.

F. It shall be the duty of the customer/user at any premises where backflow prevention devices are installed to have certified inspections and operational tests made at least once a year. In those instances where the supervisor deems the hazard to be great enough, he may require certified inspections at more frequent intervals. These inspections and tests shall be at the expense of the water user and shall be performed by the device manufacturer’s representative, by division personnel or by a certified tester approved by the supervisor. It shall be the duty of the supervisor to see that these timely tests are made. The customer/user shall notify the supervisor in advance when the tests are to be undertaken so that he or his representative may witness the tests if it is so desired. These devices shall be repaired, overhauled or replaced at the expense of the customer/user whenever the devices are found to be defective. Records of tests and repairs of backflow prevention devices should be submitted to the city for record keeping.

G. All presently installed backflow prevention devices which do not meet the requirements of this section but were approved devices for the purposes described in this chapter at the time of installation and which have been properly maintained shall, except for the inspection and maintenance requirements under subsection (F) of this section, be excluded from the requirements of these rules so long as the supervisor is assured that they will satisfactorily protect the utility system. Whenever the existing device is moved from the present location or requires more than minimum maintenance or when the supervisor finds that the maintenance constitutes a hazard to health, the unit shall be replaced by a backflow prevention device meeting the requirements of this section. (Ord. 1690 §§ 2, 3, 1989; Ord. 1330 § 2, 1976.)