15.14.060 Subsection 210.8 (A) (5) Exceptions Amended – Unfinished Portions or Areas of the Basement Not Intended as Habitable Rooms.
Subsection 210.8 (A) (5) Exceptions in the National Electric Code are hereby amended to read as follows:
210.8 (A) (5) Unfinished portions or areas of the basement not intended as habitable rooms.
Exceptions to (A) (5): The following conditions shall not be required to have ground-fault circuit-interrupter protection:
1. A receptacle supplying only a permanently installed fire alarm or burglar alarm system.
2. A single receptacle supplying a permanently installed sump pump.
3. A single receptacle supplied by a dedicated branch circuit that is located and identified for specific use by a cord- and plug-connected appliance such as a refrigerator or freezer.
Receptacles installed under exception to 2108.8 (A) (5) shall not be considered as meeting the requirements of 210.52 (G).
(Ord. 19-33 § 5, 2019; Ord. 12-46 § 2, 2012.)